Product details

Model Number: AW ASD2188-11 Brand Name: Asenware Key Specifications/Special Features: Addressable photoelectric smoke detectorAW-ASD2188 addressable smoke detector (Detector hereunder) is a kind of photoelectric smoke detector. With an internal microprocessor, it supports electronic coding and is accessed through a compatible fire alarm control panel of AW-AFP2188 via a two-wire bus.The detector realizes real-time acquisition of the in situ smoke concentration data and sends back the data to a fire alarm control panel. It can also receive and execute the control commands given by a fire alarm control panel.The detector is suitable for such industrial and civil buildings that have a great deal of smoke during fires but no smoke under normal circumstances, such as restaurants, hotels, teaching buildings, office buildings, computer rooms, communication machine rooms, libraries and archives. It is not suitable for places with a great deal of retained dust and water mist, places where steam and/or oil mist may be generated and places with retained smoke under normalcircumstances.Features:1. It can realize electronic coding and rewrite the address via coder in situ.2. Within a single-chip microcomputer, it can process the sampling data in real-time, save the latest 144 historical data and realize a curve tracing for the field situation.
3. It has a temperature, humidity and dust accumulation drift compensation function and a sensor fault detection function (fault reporting to fire alarm control panel).
4. Non-polarity, two-bus connection that ensures convenient installation and maintenance.
5. Designed with an upper cover and a lower cover and installed on an independent base, it can be installed, debugged and maintained conveniently.
Parameters
Operating Voltage 24V(Pulse Modulation)
Wiring Method Non-polarity 2-wire bus addressable system(L1,L2)
Operation Current <300μA(Monitoring Status)
Or <1.5mA(Alarm Status)
Operating Enviroment Indoor, Temperature: -10℃~+50℃, Relative Humidity: ≤95%(40℃±2℃, without Condensation)
Protection Area 60㎡
Installation
Height
≤12m
Size
(with Base)
Diameter:100mm, Height: 55mm
Weight
(with Base)
70g
Shipping Information:
  • FOB Port: Shenzhen
  • Lead Time: 3 - 5 days
Main Export Markets:
  • Asia
  • Australasia
  • Central/South America
  • Eastern Europe
  • Mid East/Africa
  • North America
  • Western Europe